Part Number: ETI0001-1444
NSN:
6130-01-511-6232
Rugged
Mil Spec® 2000 VA Integrated
Rackmount UPS and Intelligent
Power Distribution Unit Combination
Boeing / General Dynamics /
University of Texas
Navy
Rugged Mil Spec
Standard Product
Military Power®
Isolated N5 UPS Configuration
Ultra Quiet 2000 VA Rack Mount UPS w/ Integrated
6 Circuit, 2 Pole, Intelligent, Solidstate Power Distribution Unit
ETI0001-1444 Rugged Mil Spec UPS and PDU Standard Front Panel Layout
ETI0001-1444 Rugged Mil Spec UPS and PDU Standard Rear Panel Layout
Optional P/N: ETI0001-0876 UPS and PDU Remote Control Panel in 1U
The field proven Military Power® UPS line is ideally suited for military,
industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design.
These units are equally suited for use in shipboard, airborne, vehicular, field
deployed or fixed locations with controlled or uncontrolled environments.
The ETI0001-1444 was specifically designed to meet the stringent
requirements of Boeing for use in multiple programs.
The ETI0001-1444 does not require a separate PDU since the PDU
functions are already integrated into the UPS module. This saves rack space, cabling and
expense while improving overall reliability.
The heavy-duty chassis occupies only 3U (5.25”) of
rack space while delivering up to 2000 VA of clean, uninterruptible power. The front panel is sealed meeting the Navy drip proof
requirements. The
rounded metal corners and rugged handles, both front and rear, aid in safe
handling. Internally, all major components are well secured and electrically
insulated to prevent damage due to shock and vibration in any axis.
The internal shielded
input transformer provides galvanic isolation with provisions for both domestic
(115 VAC, CONUS) and optional autoranging international input voltages (85-270 VAC,
OCONUS).
The
unit also operates as a frequency converter, taking 46-70 hertz input and
converting it to 60 hertz power.
Special EMI/RFI filters and input
power factor correction minimize both input current and harmonics. The input
circuit breaker and the galvanic isolation transformer
all provide a double pole isolated source for all installations including shipboard systems or
overseas locations where phase references and grounding are not consistent.
The LED
arrays keep the operator informed as to the unit's status including load and
battery levels. The Elapsed
Time Indicator records the number of operational hours for records and
scheduling preventative maintenance of attached equipment. The
high intensity audible alarm can be heard in high noise environments and
includes an audible enable/disable switch. All controls
and protective devices are brought to the front and rear panels with critical switches or
breakers guarded. Further, all front panel devices are recessed to prevent
damage or accidental operation.
The internal intelligent PDU allows control of
the individual output circuits incorporating thermal and interlock interfaces
for additional control and safety, plus Battleshort override. Battleshort can be
engaged via the front panel control to override thermal shutdown. When in
Battleshort, an audible alarm is sounded and an indicator is lit. The display and
control panel can be mounted remotely in the rack at eye level, or on the keyboard console,
or on the unit front panel with only a logic level cable connection.
The rear panel provides locking
connectors for the input and output power with various optional configurations
available. The output connectors are unique MS threaded metal shell connectors,
each "clocked" differently so only one cable can go to each output. This
unit draws air through the side air vents and exhausts out the rear vent into the rack.
This allows the unit to be used in either positive, negative or neutral pressure
racks. The fan is a special extra quiet version to keep the unit's overall
audible level below 44 dB.
The batteries are maintenance free with immobilized electrolyte and are
constructed of flame retardant materials. For more information, see the Battery
Technology section. The
Status connector provides an
interface with optional computer software providing loss of AC and low battery status as well as
remote shut down capability. The UPS Remote Control and PDU Remote Control connectors provide an
interface to optional remote display/control panels.
See the Power Distribution Units section for a listing of
stand alone PDUs. See the N3 Series for a
version of UPS without the integrated PDU and remote control.
Overall, the Rugged Power line is uniquely qualified for critical shipboard,
vehicle, airborne or land based systems combining advanced modular design
features with highly reliable construction.
Technical Specifications:
P/N: ETI0001-1444
NSN:
6130-01-511-6232
AC OUTPUT |
Output voltage: UPS |
120 VAC true sinewave standard |
Output rating: UPS |
2000 VA, 1500 watt max standard in 3U chassis
|
Non-linear load capacity: UPS |
Up to 100% non-linear load capability w/o derating |
Output voltage regulation: UPS |
± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: UPS |
110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: UPS |
Less than 5.0% into 100% non-linear load |
Output frequency: UPS |
60 or 50 Hz ± 2.5% synchronized to utility
60 or 50 Hz ± 1.0% w/ utility not available
400 or 1000 Hz
output available as an option |
Operational status |
AC Input status, UPS operational,
UPS alarm, Battery level, Low battery, Load level, Overload, Warm
temperature, Hot temperature and Battleshort LEDs, Elapsed time hour meter
Alarm contacts for Loss of AC and Low Battery
85 dB audible alarm with audible on/off switch |
AC INPUT |
Input voltage selection: |
Nominal 115 VAC,
Optional
autoranging input of 85-270 VAC |
Input voltage tolerance: UPS |
85-135 VAC @ full load without
using battery,
Down to 70 VAC @ 75% load |
Input frequency: |
From 46 Hz to 70 Hz standard,
optional to 440 Hz |
Input power factor: |
Better than 99% typically |
Input/output isolation: |
2000 VA, up to 120 dB common mode,
<1.0 mA leakage |
Input transient suppression: |
Complies with IEEE 587, UL 1449 and
Mil Std 1399 |
Input control/protection: |
Guarded 2 pole 100 G shock rated
circuit breaker (CB1)
plus UPS input fuse (F2),
spare fuse on front
Optional cold start to turn on w/o AC present |
Input power connection: |
MS 3102A-22-2P, 3 pin, threaded locking |
INTERNAL BATTERY |
Battery type: |
Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+) |
Battery life: |
Rated for continuous service life of 5 years |
DC protection: |
Panel mounted fuse
standard, breaker optional |
Battery expansion: |
Up to 24 hours w/ Battery Expansion Modules |
DISTRIBUTION PANEL |
Output circuits: |
Six controlled outputs via solidstate relays |
Output control: |
Local/remote control panel w/rocker switches
Thermal and remote interlock ON/OFF control |
Output receptacles: |
MS3402D16-10S
MS3402D16-10SW
MS3402D16-10SX
MS3402D16-10SY
MS3402D22-2S
MS3402D22-2SW |
MECHANICAL |
Dimensions ( H x D x W ): |
5.25 (3U) x 23.5 x 19.0 in (133
x 597 x 483 mm) |
Rack Slide Mount Patterns: |
Jonathan, General Devices patterns
standard, others optional |
Alternate Mounting Options: |
Table, Wall, Floor, Portable, Horizontal/Vertical |
Unit weight: |
115 lb. (52 kg) with lift handles front and rear |
Audible noise: |
Less than 44 dB @ 5.0 ft., ANSI "A" scale |
Cooling type: |
High capacity, negative pressure, forced air |
Cooling air direction: |
Side intake, exhaust to rear,
others optional |
Air intake filter: |
Washable metal filter media, others optional |
ENVIRONMENTAL |
Storage temperature: |
-40° to 158° F ambient (-40° to 70° C) with fully charged batteries |
Operating temperature: |
32° to 126° F ambient ( 0° to
52° C), lower / higher optional |
Operating humidity: |
0 to 95% relative humidity (non-condensing) |
Storage elevation: |
Up to 40,000 ft (12,192 m) |
Operating elevation: |
Up to 15,000 ft (4,572 m), higher optional |
STANDARDS |
United States: |
Meets UL-1778 standard for UPS equipment,
MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000 |
Canada: |
CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: |
EMI/RFI FCC Part 15, Class A; EN55022; MIL
STD 461 |
OPTIONAL ACCESSORIES |
|
Autoranging International Input, Cold Start, Alternate I/O Configurations, Dual Source
Input, Battery Expansion, Batteryless Operation, Battery
Charger/Conditioner, Power Distribution Units, Software
Interface, Asynchronous serial
COM port, 10BaseT Ethernet SNMP/HTTP port,
Transport Cases, Slides
and Mounting Kits |